General specifications |
|
|
Signal type |
Analog input |
Functional safety-related parameters |
|
|
Safety Integrity Level (SIL) |
SIL 2 |
Supply |
|
|
Connection |
Power Rail or terminals 14+, 15- |
Rated voltage |
20 … 35 V DC |
Ripple |
within the supply tolerance |
Power dissipation |
1.4 W |
Power consumption |
1.8 W |
Input |
|
|
Connection side |
field side |
Connection |
terminals 1+, 2-, 3 or 5-, 6+ |
Input signal |
0/4 … 20 mA |
Voltage drop |
≤ 2.4 V at 20 mA (terminals 5, 6) |
Input resistance |
≤ 64 Ω terminals 2-, 3 ; ≤ 500 Ω terminals 1+, 3 (250 Ω load) |
Available voltage |
≥ 16 V at 20 mA terminals 1+, 3 |
Output |
|
|
Connection side |
control side |
Connection |
terminals 7-, 8+, 9 |
Load |
0 … 800 Ω at 20 mA |
Output signal |
0/4 … 20 mA (overload > 25 mA) |
Ripple |
max. 50 µA rms |